Cold water circulation valve "Aquastrom K"
DN 15, Rp ½ F x Rp ½ F, 12 - 24 °C


OVENTROP-Cold water circulation valve "Aquastrom K"

Thermostatic double regulating and commissioning valve for the hydronic balancing of chilled potable water or domestic water systems.

The valve opens above the set temperature and automatically increases the cold water volume flow. Thus, the valve allows an automatic, thermally controlled hydronic balancing in cold water circulation pipes. This way, the supply of chilled potable water at each draw off point of the system is guaranteed.

Max. water temperature: 25 °C Adjustable temperature range: 12 - 24 °C Minimum cold water volume flow kv = 0.05

All components in contact with potable water are made of non-brass materials, without dead zone, non-rising stem, maintenance-free stem seal due to double O-ring seal made of EPDM, complete with insulation shells made of EPS according to the Energy Saving Directive (EnEV), fire protection class B1 according to DIN 4102.

WRAS certified.

both ports female thread according to EN 10226-1 for intermediate ceiling installations

Material: Bronze

Size: DN 15

max. operating pressure: 10 bar
max. operating temperature: 25 °C

Item no.: 4206304
EAN: 4026755412949
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical modifications without notice.
Dimensions of article
Length Width Height Weight
90 mm 113 mm 62 mm 0,57 kg
Packing units
Type Qty. Length Width Height Weight
Carton 1 148 mm 125 mm 95 mm 0,62 kg
Product pictures
  File size
108,02 KB
  Size
1024 px x 710 px
  Properties
  •  Clear product picture
  •  Cutout
Download
Drawings
  File size
80,45 KB
  Size
940 px x 1024 px
  Properties
  •  Clear product picture
  •  Cutout
Download
Manual
  Name Size
420590480.pdf 1,94 MB
Klassifizierung
ETIM 7.0 EC011516
Thermostatic flow control valve, hot tap water
Property Value
With thermometer
Article compression class PN 10
KIWA certified
With drain
Handle/hand wheel height 67 mm
With measuring connector
Setting can be locked
With thermometer connection
Temperature setting range 12 - 24
Min. flow
Disinfection function None
With connection 2 coupling
Housing material Bronze
With position indicator
With measuring nipples
Nominal inner diameter DN 15