Logo Oventrop GmbH & Co. KG

Regudis W-HTU Basic Dwelling station
performance range 3, 17 l/min., heat exchanger copper brazed


For the supply of individual dwellings or commercial units with heating water, as well as with hot and cold potable water. The required heat is provided by a central heat supply. Hot potable water is prepared decentrally via a plate heat exchanger according to the continuous flow principle. When selecting the dwelling station, it is necessary to consider the water quality of the area of use.

The stations consist of a plate heat exchanger, a proportional flow controller for hydronic control of hot potable water preparation, a thermostatic temperature controller, filter inserts, spacers for heat and water meter, a zone valve for heating circuit control, a differential pressure control valve, vent valves and drain valves.

The Regudis W-HTU dwelling stations are designed for unmixed heating circuits and are ideal for replacing existing gas boilers in building refurbishment projects. They are characterized by high-quality materials and are completely mounted on a base plate. The stations are tested for tightness and function.

  • Performance range: Performance range 3
  • Nominal draw-off quantity heating of potable water 10 °C/50 °C with ∆T 15 K (according to SFP test procedure): 17 l/min
  • Heating circuit: Unmixed
  • Heat exchanger: Copper brazed
  • Heat exchanger, double-walled: No
  • Connections: Internal thread
  • Supply connections: Bottom
  • High temperature outlet: Yes
  • Proportional flow controller: Yes
  • Integrated differential pressure control valve: No
  • Temperature control: Thermostatic
  • Setting range: 40 - 70 °C
  • Spacer for heat meter: Yes
  • Spacer for water meter: No
  • Filter insert: Yes
  • Safety valve: No
  • Max. operating temperature: 90 °C
  • Max. operating pressure: 10 bar
  • Min. differential pressure supply: 150 mbar
  • Leak tested: Yes
No longer produced
Art.-Nr.: 1340932
EAN: 4026755423228
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical changes

Dimensions

Dimensions of article

Length Width Height Weight
150 mm 476 mm 630 mm 14,71 kg

Packing units

Type Qty. Length Width Height Weight
Carton 1 170 mm 490 mm 660 mm 16,86 kg

Images

Product images

  File size
819,84 KB
  Size
3543 px x 3543 px
  Properties
  •  Clear product picture
  •  Cutout
Download

Drawings

  File size
96,42 KB
  Size
675 px x 929 px
  Properties
  •  Clear product picture
  •  Cutout
Download

ETIM

Klassifizierung
ETIM 7.0
Property Value
Width 476 mm
Model Indirect
Height 645 mm
Depth 140 mm
Suitable for CH/tap water
With adapter for heat meter
With heat meter
Tap water power 42 kW
Adjustment range hot water temperature 40 - 70
Nominal internal diameter hot tap water 3/4 inch (20)
Nominal inner diameter cold tap water 3/4 inch (20)
Tap capacity at 60°C, continuous 17 l/min
Max. operating pressure 1000 kPa
Exchanger with dual separation
Nominal inner diameter heating 3/4 inch (20)
Nominal inner diameter of supply 3/4 inch (20)
Nominal inner diameter return 3/4 inch (20)