Electrothermal actuator "Aktor T ST"
"L NC", 24 V, closed with current "off", 0-10 V, with automatic recognition of neutral point and valve travel


OVENTROP-Electrothermal actuator "Aktor T ST" "L NC", 24 V, closed with current "off", 0 - 10 V

With automatic recognition of neutral point and valve travel.

The actuator (0 - 10 V) can be used in centralised building control systems in combination with the electronic room thermostat, item no. 1152151/53, or with a central controller.

Plug-in connecting cable 1 m. With First-Open function and stroke index. Easy plug-in connection with valve adapter.

Due to their construction, the electrothermal actuators are secured against overvoltage which could occur when switching on neon tubes. A varistor is thus not necessary.

Item no.: 1012953
EAN: 4026755423365
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical modifications without notice.
Is accessory of
Dimensions of article
Length Width Height Weight
60 mm 62 mm 45 mm 0,12 kg
Packing units
Type Qty. Length Width Height Weight
Carton 1 90 mm 75 mm 52 mm 0,13 kg
Europallet 500 1200 mm 800 mm 820 mm 94 kg

Notice for CAD viewer

In order to open the CAD-Viewer and Download CAD-Data please onetime download and install the CAD-App.

Product pictures
  File size
114,24 KB
  Size
3368 px x 3368 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
114,24 KB
  Size
3368 px x 3368 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
84,58 KB
  Size
2612 px x 2612 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
131,91 KB
  Size
2688 px x 2688 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
133,25 KB
  Size
2612 px x 2612 px
  Properties
  •  Clear product picture
  •  Cutout
Download
Drawings
  File size
13,97 KB
  Size
207 px x 224 px
  Properties
  •  Clear product picture
  •  Cutout
Download
Technical data
Manual
  Name Size
101295380.pdf 672,1 KB
Klassifizierung
ETIM 7.0 EC010193
Thermal servomotor
Property Value
Colour White
Width 44.3 mm
Model Filled with washing
Function Deactivated when closed NC
Height 58.1 mm
Nominal power 1 VA
Control signal 0-10 V
Cable length 1 m
Length 61.5 mm
Ambient temperature 0 - 60
Manual operation
Degree of protection (IP) IP54
Automatic travel recognition
Protected against overvoltage
Connection to stop valve M30 x 1.5
First open
Stroke length 5 mm
With position indicator
With end contacts
Max. electric power input 7.7 VA
Supply voltage 24 V AC
Auxiliary contacts