Logo Oventrop GmbH & Co. KG
Download GAEB

Double regulating valve HydroControl VFC
PN 16, DN 400, Flange EN 1092-2, Kvs: 3750

For hydronic balancing of distribution pipes in central heating and cooling systems with closed circuits. Determination of the flow rate by measuring the differential pressure with the help of the measuring system OV-DMC 3 taking the preset values into consideration.
Y-pattern valve with secured, at any time controllable, infinitely adjustable fine presetting. All functions accessible from the top. Supplied with two auxiliary valves.

  • Main function: Double regulating valve
  • Medium: Water, Water-glycol mixture
  • Pressure rating: PN 16
  • Nominal size: DN 400
  • Connections: Flange EN 1092-2
  • Kvs: 3750
  • Operating temperature: -10 - 150 °C
  • Pressure rating flange: PN 16
  • Presetting: Yes
  • Reproducible presetting: Yes
  • Presetting blockable: No
  • Presetting indicator: Yes
  • Shutoff: Yes
  • Measuring connection: Yes
  • Measuring valve: Classic
  • Measuring method: Flow rate determination by differential pressure measurement
  • Draining: Extendable (only depressurized)
  • Impulse tube connection: Extendable (only depressurized)
  • Body material: Nodular cast iron
  • Type: Y-pattern
  • Installation location: Supply or return
  • Insulation shell: No
  • Installation position: Position-independent

Art.-Nr.: 1062660
EAN: 4026755514742
Hersteller: Oventrop GmbH & Co. KG
Technische Änderungen vorbehalten