Double regulating valve HydroControl V
PN 25, DN 25, Internal thread, Kvs: 10.8
Variable orifice double regulating valve for the hydronic balancing of pipelines in closed central heating and cooling systems. Optional flow measurement, for example with the OV-DMC3 measuring system. Installation in supply or return.
Flow optimised Y-pattern housing. Valve insert with continuous, superfine pre-setting and non rising handwheel. Permanently visible pre-setting value, also when valve is insulated. Reproducible, lockable and sealable presetting position as standard. All functions operable from handwheel side. Fitted with two measuring, fill and drain valves as standard. Valve housing and all parts with contact to the flow made of dezincification resistant brass, PTFE or EPDM. Maintenance free, double spindle sealing.
Inlet and outlet with internal threads to NPT.
Size: 1” (DN25)
Connection: NPT 1“ internal threads
Cv value: 12.7
Specifications
- Operating temperature: -4…302°F (-20…150°C)
- Operating pressure: max. 363 psi (25 bar)
- Characteristic: linear
- Leakage rate A to EN 12266-1, P12 (no visible leakage)
Functions
- Regulate
- Pre-setting
- Shutoff
- Measuring
- Filling, draining, venting
- Quick impulse tube connection for suitable differential pressure control valves
Material
- Housing, insert and measuring valves: DZR brass, untreated
- O-Ring sealings: EPDM
- Seat sealing: PTFE
- Handwheel assembly, protection caps: PA6
Art.No.: 1062908
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical changes.