Logo Oventrop GmbH & Co. KG

Regumat F-130 DN 25 Station for fixed value control
with Grundfos ALPHA 2.1 25-60


Boiler connection system "Regumat F-130"

Fixed value control unit "Regumat F-130" for flow temperature control and limitation in combined radiator/surface heating systems. The flow temperature is controlled with the help of a three-way mixing valve in combination with a temperature controller with immersion sensor.

Consisting of: -Isolation device with 2 ball valves and 2 thermometers (without pressure relief device) and connection for immersion sensor -Temperature controller with immersion sensor -Flanged pipe with check valve -Three-way mixing valve -Electronic pipe contact safety switch -Insulation

Ball valves: Body and stem made of brass with double O-ring seal, chrome plated brass balls, PTFE seats, collar nuts made of brass.

Distance between pipe centres: 125 mm Connection to the heating circuit: G 1½ male thread, flat sealing Connection to the boiler: G 1½ male thread, flat sealing

Opening pressure of the check valve: 20 mbar

Control range: 20 - 50 °C
No longer produced
Art.No.: 1354165
EAN: 4026755355604
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical changes.

Dimensions

Dimensions of article

Length Width Height Weight
429 mm 248 mm 200 mm 7,16 kg

Packing units

Type Qty. Length Width Height Weight
Carton 1 446 mm 273 mm 245 mm 7,64 kg

Images

Product images

  File size
1,8 MB
  Size
4556 px x 3166 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
510,15 KB
  Size
1948 px x 1537 px
  Properties
  •  Clear product picture
  •  Cutout
Download

Drawings

  File size
93,86 KB
  Size
595 px x 1008 px
  Properties
  •  Clear product picture
  •  Cutout
Download

Characteristic curves

Loss of pressure

Please wait a moment...
Characteristic line is queried

ETIM

Klassifizierung
ETIM 7.0 EC001110
Compact installation for heat pump
Property Value
Width 248 mm
Height 364 mm
Depth 197 mm
Connection 1 1/2 inch
With thermal insulation
With thermometer
Connection to Heating circuit
With circulation pump
With safety valve
With pressure gauge
With non-return valve
With filling- and draining valve
Max. flow rate 2.2 m³/h
With connection expansion reservoir
With automatic de-aeration