Logo Oventrop GmbH & Co. KG

Regudis H-HT Transmission station for local heating
max. performance range 45 kW


Transmission station with plate heat exchanger for indirect heat transmission from a local or district heating network to the potable water and heating system of detached and semi-detached houses.

Primary-side connection option for direct hot potable water preparation using the storage cylinder principle.

The stations are equipped with an electronic controller for the weather-compensated control of the flow temperature of the heating system and simultaneous limitation of the return temperature to the heat network. Optional hot water priority circuit or parallel operation to the heating circuit. Use in closed local and district heating networks. For operation with non-aggressive, non-hazardous media (e.g. water or suitable water-glycol mixtures according to VDI 2035 / ÖNORM 5195).

Nominal size: DN 20
Operating pressure primary side: PN 10
Safety valve secondary side: 3 bar
Max. primary temperature: 90 °C

Performance range:
Max. 30 kW (with primary: 75/45 °C, secondary: 65/35 °C)
Max. 45 kW (with primary: 90/45 °C, secondary: 80/35 °C)

Pressure gauge display range: 0 - 10 bar
Heat network and house connection: G ¾

Dimensions (W x H x D): 470 mm x 680 mm x 295 mm
No longer produced
Art.No.: 1391025
Manufacturer: Oventrop GmbH & Co. KG
Subject to technical changes.

Dimensions

Dimensions of article

Length Width Height Weight
675 mm 465 mm 295 mm 17,34 kg

Packing units

Type Qty. Length Width Height Weight

Images

Product images

  File size
1,8 MB
  Size
5555 px x 5555 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
4,82 MB
  Size
7891 px x 7891 px
  Properties
  •  Clear product picture
  •  Cutout
Download
  File size
3,13 MB
  Size
5739 px x 5739 px
  Properties
  •  Clear product picture
  •  Cutout
Download

Drawings

  File size
25,61 KB
  Size
303 px x 373 px
  Properties
  •  Clear product picture
  •  Cutout
Download

ETIM

Klassifizierung
ETIM 7.0
Property Value
Width 470 mm
Model Direct
Height 680 mm
Application District and block heater
Depth 295 mm
Suitable for CH/tap water
Connection feed/return heating Internal thread
Connection supply Internal thread
Connection return Internal thread
Max. heating power 45 kW
With adapter for heat meter
With heat meter
Nominal internal diameter hot tap water 3/4 inch (20)
Nominal inner diameter cold tap water 3/4 inch (20)
Max. operating pressure 1000 kPa
Exchanger with dual separation
Cold tap water connection Internal thread
Hot tap water connection Internal thread
Nominal inner diameter heating 3/4 inch (20)
Nominal inner diameter of supply 3/4 inch (20)
Nominal inner diameter return 3/4 inch (20)